| Applications |
| |
 |
Parkings |
| |
 |
Industrial and commercial kitchens |
| |
 |
Officially approved to EN12101-3 standard (certificate number 0370-CPD-0348) |
| |
 |
Under request |
| |
 |
Under request |
| |
| |
|
|
|
| Documentation |
| |
| |
| |
|
|
| |
| Description |
| |
| |
| |
THGT Series Adjustable Pitch F400-120, F300-120 and F200-120 Rated Fans Range of adjustable pitch cased axial flow fans designed for smoke extraction in fire conditions and certified F400-120, F300-120 and F200-120 (CE marked). Casings formed from rolled sheet steel with a corrosion resistant hot dipped galvanised finish for all models. All models F400-120 except 2 poles incorporate separate high grade die-cast aluminium blades locked within an aluminium injected hub (diameters from 400 to 630) or a pressed sheet steel hub.(diameters from 710 to 1250). F300-120 and F200-120 models incorporate an aluminium injected hub (diameters from 400 to 800) or a pressed sheet steel hub. (diameters from 900 to 1250). 2 POLES F400-120 model with aluminium impeller / hub formed from a one piece casting. All models are available in both short and long (L) casing versions except 2 poles F400-120 model only with long casing. Suitable for horizontal or vertical mounting installation. |
| |
| Motors |
| |
| |
| |
Available, depending upon the model:
- with three phase motors in 2, 4, 6 or 8 poles.
- with three phase two speed motors 2/4, 4/6, 4/8 or 6/12 poles.
F400-120 motors are IP55, class H insulation. F300-120 motors are IP55, class H insulation. F200-120 motors are IP55, class F insulation. Electrical supplies:
- Three phase 230/400V-50Hz up to 3 kW.
- Three phase 400V-50Hz, for higher power
motors and two speed motors. (See characteristics chart). Motors suitable for inverter control. In emergency operation, recommend direct protected power supply. |
| |
| Additional Information |
| |
| |
| |
Standard air direction: form (B) configuration(Impeller over Motor). On request Air direction: form (A) configuration (Motor over Impeller). Short casing with exterior terminal box. Motors EFF1 under request. THGT 2 Poles F400 120 Cased axial fan rated F400-120 for smoke extraction in fire condition. Long casing formed from rolled sheet steel with a corrosion resistant hot dipped galvanised finish. Aluminium Impeller / hub formed from a one piece casting. Motors Available, depending upon the model:
- with three phase motors in 2 poles.
- with three phase two speed motors in 2/4
poles. F400-120 motors are IP55 - Class H insulation. Electrical supplies:
- Three phase 230/400V-50 Hz up to 3 kW.
- Three phase 400V-50Hz, for higher power
motors and two speed motors. |
| |
 |
|
| Motor approved S1 and S2 |
| |
| F400-120, F300-120 or F200-120 certified motors approved for running continuously (S1) or for emergency operation (S2) |
|
| |
| |
| |
 |
|
| Corrosion resistance |
| |
| Casings formed from rolled sheet steel with a corrosion resistant hot dipped galvanised finish |
|
| |
| |
| |
 |
|
| Aerodynamic motor support |
| |
| Aerodynamic design of the motor support to optimise airflow performances F400-120 models from 710 to 1250. F300-120 and F200-120 models from 900 to 1250 |
|
| |
| |
| |
 |
|
| Motor support |
| |
| Manufactured from electrowelded sheet steel. F400-120 models from 400 to 630 F300-120 and F200-120 models from 400 to 800 |
|
| |
| |
| |
 |
|
| Impeller dynamically balanced |
| |
| Impeller dynamically balanced, according to ISO 1940 standard, providing vibration free operation |
|
| |
| |
| |
 |
|
| Wide blade design: higher pressure |
| |
| Wide blade design to ensure the highest efficient airflow performances |
|
| |
| |
| |
 |
|
| Hub impeller protection |
| |
| Flat hub impeller to prevent the accumulation of dirtiness |
|
| |
| |
| |
 |
|
| Large inspection door |
| |
| Fitted on long cased models, gives access to the motor and eases the wiring motor connection. Supplied with cable gland |
|
|
| |
|