| Applications |
| |
 |
Parkings |
| |
 |
Industrial and commercial kitchens |
| |
 |
Drying installations |
| |
 |
Iron and steel industries Foundries |
| |
 |
Cooling of motors, compressors or other electrical machines |
| |
 |
Welding installations |
| |
 |
Ventilation and cooling of working places |
| |
 |
Car industry / Furnace ventilation |
| |
 |
Officially approved to EN12101-3 |
| |
 |
Continuous operation |
| |
| |
|
|
|
| Documentation |
| |
| |
| |
|
|
| |
| Description |
| |
| |
| |
Range of single inlet direct drive centrifugal fans designed for smoke extraction in fire conditions and certified F400 120 (CE marked) and suitable for the continuous extraction of air stream up to 300ºC. All casings are manufactured from electro-welded sheet steel protected against corrosion by grey epoxy-polyester paint coating. All models incorporate forward curved centrifugal impellers manufactured from galvanised sheet steel. Available, depending upon the model, with single or three phase motors in 4 or 6 poles. |
| |
| Motors |
| |
| |
| |
All motors are IP55, class F. Electrical supply:
- Three phase 230/400V-50Hz up to 3kW.
- Three phase 400V-50Hz, for higher power motors.
(See characteristics chart). |
| |
| Additional Information |
| |
| |
| |
The scroll can be orientated in 8 different positions as per the table below. Standard supplied position: LG 270. On request
- Fan supplied in RD position.
- Fan fitted with 2-speed motor.
|
| |
 |
|
| Standard motor with cooling wheel |
| |
| Motor heat removal system ensures extraction of high temperature air stream |
|
| |
| |
| |
 |
|
| Impellers dynamically balanced |
| |
| Forward curved centrifugal impellers dynamically balanced according to ISO 1940 standard, providing vibration free operation. |
|
|
| |
|